AROS Solar Technology
AROS Solar Technology (RS485)
8�2 AROS Solar Technology (RS485)
Easy Installation Termination Addressing Interface
No Yes No
RS485
Select "Aros 485" during the inverter detection
Overview
•
Integrated interface
•
Where to connect: Terminal strip inside the inverter
•
3-pin wiring
•
Communication address does not have to be assigned
Note:
The order in which the inverters are displayed in the Solar-Log™ after detection is random.
We strongly recommend that you change the order of the inverters immediately after de-
tection at startup in the Configuration | Device | Configuration | Order menu box.
The inverters can be identified using the displayed serial number.
•
Installation steps
• Switch off the inverters and Solar-Log™
• Connect inverters to the Solar-Log™
• Connect the inverters to each other
Connect inverters to the Solar-Log™
The wiring is done using a
•
self-made cable connection with terminal block connector.
Procedure
1. If you are making the cable yourself, connect the wires as shown in the following diagram:
Solar-Log™ terminal strip connector RJ45 inverter
Terminal PIN
1 A (+)
3 GND
4 B (-)
2. If only one inverter is to be connected terminate this in accordance with the inverter instructions.
3. Insert the terminal block connector into the Solar-Log™ RS485 socket.
Connect the inverters to each other
•
Connect using a 3 wire, shielded data cable
•
Where to connect: Terminal strip inside the inverter